Engineering & testing

Railing Masters guard systems are supported by independent field load testing and P.Eng-stamped detail packages. This page publishes the measured results in full.

Reviewed & stamped PEO 100206138 31 July 2025
Stamped review

F. Alibai, P.Eng. · PEO 100206138

Review by JRAMCO Inc. for the sole purpose of framing, glass and anchor structural adequacy, in general conformance with OBC and CDS.

Design wind load
2.0 kPa
Post spacing
1080 mm
Post height
1070 mm
Drawing packages are project-generic. For a specific project, design is to be reviewed and approved by the project’s professional engineer.
Field load test · report RT25-330-1111-01

All seven load cases passed.

Static load testing performed by JRAMCO Inc. at 110 Claireport Crescent, Unit 4, Etobicoke, Ontario on 11 November 2025, in general conformance with ASTM E935-13 and ASTM E985.

2.1 kN 1.78 kN 1.96 kN 0.9 kN int. post end post mid-span glass, 100 × 100 mm 1080 mm 1070 mm
Where the loads were applied. Horizontal loads at guard height, inward and outward, at an intermediate post, an end post and the top rail at mid-span; the glass load over a 100 × 100 mm area at panel centre. Guard height 1070 mm, post spacing 1080 mm.
Intermediate post
Outward · Table 1A
2.1 kN
PASS
Intermediate post
Inward · Table 2A
2.1 kN
PASS
Top rail, mid-span
Outward · Table 1B
1.96 kN
PASS
Top rail, mid-span
Inward · Table 2B
2.1 kN
PASS
End post
Outward · Table 1C
1.78 kN
PASS
End post
Inward · Table 2C
1.78 kN
PASS

marks the OBC 4.1.5.14 minimum of 1.0 kN. Bars show the load actually applied.

Glass infill: concentrated load

Tested at 0.9 kN against a 0.5 kN code requirement, applied over a 100 mm × 100 mm area at panel center.

Applied load
0.9 kN (203 lb)
Code minimum
0.5 kN
Net deflection
2.09 mm
Residual
0.09 mm

No cracking, delamination or distress at glass holders, channels or mechanical connections.

Test assembly

  • Structural aluminum posts and top rail manufactured by Hydro Extrusions
  • Laminated glass infill panels
  • Mechanically fastened structural connections
  • Mechanical anchorage into reinforced concrete slab
Anchor
Hilti KB3 wedge anchor, ½" × 4½"
Embedment
3" (76 mm)
Substrate
6" reinforced concrete slab
Measured deflection

A fraction of what the standard allows.

Deflection limits per CSA A500-16, Clause 5.5.1.6. Lower is better; the bar shows measured deflection as a share of the allowable limit.

TableElementDirectionApplied DeflectionAllowableUtilizationResidualResult
1A Intermediate post Outward 2.1 kN 26 mm 89 mm
29%
1.5 / 13 mm PASS
2A Intermediate post Inward 2.1 kN 27.5 mm 89 mm
31%
1.5 / 13 mm PASS
1B Top rail, mid-span Outward 1.96 kN 36 mm 56 mm
64%
1.5 / 11 mm PASS
2B Top rail, mid-span Inward 2.1 kN 36.5 mm 56 mm
65%
1 / 11 mm PASS
1C End post Outward 1.78 kN 30.5 mm 89 mm
34%
1.5 / 13 mm PASS
2C End post Inward 1.78 kN 19 mm 89 mm
21%
4.5 / 18 mm PASS
C Glass infill, center Outward 0.9 kN 2.09 mm — Serviceability: minimal 0.09 mm PASS

Test configuration: guard height 1070 mm, post spacing 1080 mm. Deflections measured with calibrated laser displacement equipment.

Standards

Tested and designed to

ASTM E935-13Performance of Permanent Metal Railing Systems
ASTM E985Specification for Permanent Metal Railing Systems
OBC 4.1.5.14Ontario Building Code (2012), Loads on Guards
CSA A500-16Deflection criteria, Clause 5.5.1.6
CSA S157Strength design in aluminum
Code requirements

OBC 4.1.5.14, loads on guards

  • 0.75 kN/m or 1.0 kN concentrated load, whichever governs, applied horizontally at guard height
  • 0.5 kN concentrated load applied over a 100 mm × 100 mm area to individual elements (glass infill)
  • Specified wind load pressure of 2.0 kPa
  • Vertical load provisions reviewed per OBC Clause 4.1.5.14(4)
Procedure

How the test was run

  • Horizontal loads applied incrementally and held until stabilization was achieved
  • A preload of approximately 50% of target load applied and released prior to final loading, to assess residual deflection
  • Deflections measured using calibrated laser displacement equipment
  • Loads increased gradually to the maximum calculated design load, then released to observe permanent deformation or connection distress
Observations

What was recorded

  • Measured deflections remained within allowable limits for all load cases
  • Residual deflection after load release was within acceptable tolerances
  • No structural failure, cracking, yielding, loosening or disengagement of posts, anchors, top rail, glass panels or mechanical connections was observed
  • Glass infill panels resisted the specified 0.5 kN concentrated load without damage or instability
  • Load–deflection behavior was linear and stable throughout each test
Based on field testing observations and measured performance, JRAMCO Inc. confirms that the tested Railing Masters Inc. aluminum balcony guardrail system complies with the structural performance requirements of the Ontario Building Code (2012) and applicable ASTM standards. The system demonstrates adequate strength, stiffness, and connection integrity under prescribed service loads and is considered structurally satisfactory for its intended application.

— JRAMCO Inc., Field Test Report RT25-330-1111-01. Certified mill test reports from Hydro Extrusions are available on request and confirm that all aluminum extrusions supplied are within specified alloy and temper tolerances and meet applicable material standards.

Stamped packages

Four detail sets, reviewed and stamped.

Elevation and section sheets from each package. The full sets, with connection details and materials lists, are on the resources page.

Top of Slab Railing, stamped elevation and section sheet
Top of Slab Railing · sheet TR-01 / TR-02 · rev. 01
Face of Slab Railing, stamped elevation and section sheet
Face of Slab Railing · sheet FR-01 / FR-02 · rev. 02
Picket Railing, stamped elevation and section sheet
Picket Railing · sheet PL-01 · rev. 02
Balcony Privacy Divider, stamped elevation and section sheet
Balcony Privacy Divider · sheet M.L. · rev. 01
Component schedule

Component schedule

Extracted from the stamped materials lists. Fastener schedules are the standard specification; project-specific engineering may vary them.

ComponentAlloySpecification
Base plate6061-T6Anchored to concrete with 2 × ½"⌀ (13 mm) × 3¼" Hilti Kwik Bolt TZ stainless expansion anchors, 89 mm embedment, with lock and flat washer.
Railing post6061-T6Base plate bolted to post with 4 × ⁵⁄₁₆"–18 × 1¾" unpainted fully threaded S.S. T316 bolts, washer and lock washer. 4 × ⅜"–18 tapped to min. 1⅝".
Glass rail holder6061-T6Fastened to post with 4 × #12 × 1" painted pan-head self-tapping stainless screws.
Glass channel6061-T6Fastened to glass rail holder with 2 × #10 × ½" painted pan-head self-tapping stainless screws.
Hand rail6061-T6Fastened to post clip anchor with 2 × #10 × ¾" painted pan-head self-tapping stainless screws.
Post clip anchor6061-T6Installed at top of post, fastened each side of post and to underside of handrail with 2 × #10 × ¾" painted pan-head self-tapping stainless screws.
Connecting sleeve, 127 mm6061-T6Expansion joint at every 50 ft (1520 mm), fastened with 2 × #10 × ¾" screws on one side only. Located where handrail is mounted between two posts; 4 × #10 × ¾" screws, 2 each side.
Corner sleeve, 160 mm6061-T6Fastened to handrail with 4 × #10 × ¾" pan-head self-tapping stainless screws, 2 screws each direction.
End cap6061-T6Painted end cap fastened to stainless angle with 2 × #10 × ¾" painted pan-head self-tapping stainless screws.
Stainless angleS.S.25 mm × 25 mm × 2 mm thick × 76 mm long, fastened to end cap and to underside of handrail with #10 × ¾" screws.
Glass patch6061-T65 mm neoprene gasket, 3 mm painted aluminum flat 100 × 100 mm, 1.5 mm double-sided tape each side of glass; fastened to post with 2 × #12 × 1¾" painted flat-head self-tapping stainless screws.
Gaskets & shims—1.5 mm double-sided tape between glass rail holder and glass channel. PVC horseshoe shims between glass channel and rail holder. Channel gasket inserted into glass channel; rubber gasket at each glass end.
Specify with confidence

Send us the elevation. We'll send back the system.

Tell us the mounting condition, guard height and code jurisdiction. We'll come back with the recommended system, a stamped detail set and a materials list you can put straight into the spec.

Sales & project enquiriesjames@railingmasters.ca
Office416.674.0718
Mobile647.838.7345
Plant & office110 Claireport Crescent, Unit #4, Etobicoke, ON M9W 6P3